Inspection #: 790559
Inspection Type: Electrical Inspection
Inspector: M.Green
Result: Approved
Comment: Building is completely generator backed-up. Battery back-up troffers appear to be night light circuits. Floors 4,5,7, and 8 one-for-one troffer lighting replacement on existing circuits complete and approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/19/2024CorrectedCorrect following Item  8th floor south side and lobby EM lights.Fed from Panel XA in penthouse. XA is not an emergency panel due to types of loads served. Area normal lights are supplied from an 8th floor panel. Circuits not compliant with 700.12(I).
1/19/2024CorrectedCorrect following Item  8th floor circuits from 8th floor panel that serve emergency lights.Same concerns as 7th floor lighting circuits.
1/19/2024CorrectedCorrect following Item  7th floor battery back-up troffers.2020 NEC 700.12(I)(3) permits unit equipment to be on a circuit other than the normal lighting circuit if: 1. Served by a separate EM lighting circuit. 2. EM lighting circuit to be from same panel as normal lighting circuits. 3. EM lighting circuit required to be clearly identified. 4. EM lighting circuit required to have a lock-on feature. VERIFY COMPLIANCE WITH 700.12(I).
1/19/2024CorrectedCorrect following Item  7th floor corridor north end.Missing battery back-up troffer that is shown on drawings.