Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 789664
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Corrections made- new corrections required for phase 2. Electrical final conditionally approved for public occupancy pending completion of noted items.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/25/2024TransferCorrect Below*  Platform required at rooftop condensing units so that centerline of disconnect handle is no greater than 6'7" from working platform.
1/25/2024TransferCorrect Below*  No power at receiving mandoor exit light.
1/25/2024TransferCorrect Below*  Main entry and receiving air doors incomplete.
1/25/2024TransferCorrect Below*  Compressor A and C require 200A max breakers.
1/25/2024TransferCorrect Below*  Shore power service and associated hook ups incomplete.
1/25/2024TransferCorrect Below*  Truck plugs at loading docks incomplete.
1/25/2024TransferCorrect Below*  Conveyor system not permitted to be fed with flexible cords. Flexible cords not permitted as substitute for fixed wiring methods.
1/25/2024TransferCorrect Below*  Bailer and compactor disconnects required bonding bushings.
1/25/2024TransferCorrect Below*  Bailer and compactor installation incomplete.
1/9/2024CorrectedCorrect Below*  Ceiling fan incomplete.
1/9/2024CorrectedCorrect Below*  Phase 2 incomplete.
1/9/2024CorrectedCorrect Below*  Rooftop incomplete.
1/9/2024TransferCorrect Below*  Conveyor system incomplete.
1/9/2024TransferCorrect Below*  Heat trace incomplete.
1/9/2024CorrectedCorrect Below*  3 cage registers incomplete.
1/9/2024CorrectedCorrect Below*  Freezer units at front entry to be relocated.
1/9/2024CorrectedCorrect Below*  Entry heaters and exit signs incomplete.
1/9/2024CorrectedCorrect Below*  Exterior entry lighting incomplete.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS