Inspection Type: Hood and Duct Fire System Final
Inspector: B.Meinhardt
Result: Correction
Comment: REQUESTING 10:00 AM FINAL INSPECTION Requested by: Tyrel Laret 907-575-8785 tyrel@northstarfireprotection.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
5/29/2024TransferHoodDuctFire12Correction(s) #3Correct the following item(s): Notes only:&nbsp;&nbsp;<div>(1) Main line kitchen electric gas shut off controlled by CaptiveAir controller on hood.&nbsp; &nbsp;Manual pull station located at rear kitchen exit door.&nbsp; &nbsp;K-Class located at rear exit door.&nbsp; &nbsp;(2) Southside dinning room electric gas shut off controlled by buckeye gas controller on dishwashing area.&nbsp; &nbsp;2 nozzles located on each side of table filters with an electronic heat detector.&nbsp; &nbsp;2 pull stations located south dinning room columns. (3) Northside dinning room electric gas shut off controlled by buckeye gas controller on storage room.&nbsp; &nbsp;2 nozzles located on each side of table filters with an electronic heat detector.&nbsp; &nbsp; 2 pull stations located north dinning room columns.</div>
5/29/2024TransferHoodDuctFire18Install Cert<div>Provide Installation Certification and test report.</div><div><br></div> Need installers cert for each system
5/29/2024TransferHoodDuctFire11Correction(s) #2Correct the following item(s): Dining room tables area corrections:&nbsp; (1) Need to install pull station guards&nbsp; (2) need to install signs on the pull stations identifying northside and southside pull stations&nbsp;
5/29/2024TransferHoodDuctFire10Correction(s) #1Correct the following item(s): Mainline cooking hood corrections:&nbsp; (1) floor need to be permanently marked for appliance locations to keep appliances 6 inches inside of hood and nozzle alignment.&nbsp; (2) Nozzles need to be re-piped to align with appliances per installation manual&nbsp; (3) need splash shield between the fryer and gas range.