Inspection #: 788633
Inspection Type: Electrical Inspection
Inspector: M.Green
Result: Correction
Comment: Please call Joel in the morning to schedule a time to meet. Joel (907 203-0120) will meet for the inspection, but he's coming in from the valley so a time slot would be appreciated! Thanks! Tony Requested by: Tony Noethlich (907) 336-1258 tn@sei-ak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/10/2024TransferCorrect following Item  Circuits supplying battery back-up luminaires.Could not verify proper circuitry. May need an early inspection to be able to turn off circuits.
12/27/2023TransferCorrect following Item  4th floorNo power at emergency lights at grid 4D and 5B.
12/27/2023TransferCorrect following Item  Elevator lobby on 4th floorEmergency lighting must be on local lighting circuit or on dedicated circuit in an area with no less than 3 lighting circuits.
12/27/2023TransferCorrect following Item  ThroughoutAll luminaires require 2 seismic wires installed on opposite corners. Additionally, either all 4 tabs must hook over and under the top edge of the grid or have the other 2 corners screwed to the grid. UPDATE TO THIS CORRECTION: 4TH AND 8TH FLOOR SPOT CHECK REVEALED NUMEROUS LIGHTS NOT SCREWED TO GRID AND WITHOUT (4) TABS ENGAGED WITH THE CEILING GRID. (1) FIXTURE WITH SEISMIC WIRES NOT ON OPPOSITE CORNERS.