Inspection #: 787712
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Elevator modernization. Corrections as below.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/12/2024TransferCorrect Below* Panel schedule on drawings.Shows 200A breaker for elevator. 175A breaker installed to match ampacity of wire (2/0). Change drawings to indicate actual installation.
1/12/2024TransferCorrect Below* Parent permit.M23-1927 appears to be incorrect. Correct parent permit appears to be C23-1927.
1/12/2024TransferCorrect Below* Address.Shown as 3601 Residential Drive. Actual project address is 3701 Residential Drive.