Inspection #: 787121
Inspection Type: Electrical Inspection
Inspector: M.Green
Result: Approved
Comment: ETL responded stating that the field conversion from 230V, 1-phase to 480V, 3-phase does not violate the listing of the unit. RTU replacement electrical installation complete and approved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/8/2023CorrectedCorrect following Item  Rupp RTU voltage change.Unit ordered as 230V 1-phase with internal VFD that provides 3rd phase to motor. Unit has been field converted to run on a 480V, 3-phase circuit by replacing the VFD. Does ETL regard this unit as a listed product after a VFD change?