Inspection #: 786406
Inspection Type: Electrical Inspection
Inspector: M.Green
Result: Correction
Comment: Waiting to hear back from Rupp rep. Colton Borg. 612-481-2617 regarding issue below. Contractor will need to request another inspection after Rupp rep. provides answers.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/8/2023TransferCorrect following Item  Rupp RTU voltage change.Unit ordered as 230V 1-phase with internal VFD that provides 3rd phase to motor. Unit has been field converted to run on a 480V, 3-phase circuit by replacing the VFD. Does ETL regard this unit as a listed product after a VFD change?