Inspection #: 784085
Inspection Type: Electrical Inspection
Inspector: O.Burbridge
Result: Correction
Comment: Late afternoon inspection please. We're on nights, and Justyn will be coming in from the valley for the inspection, so if possible, please give plenty of heads-up or schedule a time to meet on site for the inspection. (907) 802-9022 Requested by: Tony Noethlich (907) 336-1258 tn@sei-ak.com Requested by: Tony Noethlich 9073361258 Tn@sei-ak.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
12/27/2023TransferCorrect following Item  4th floorNo power at emergency lights at grid 4D and 5B.
12/27/2023TransferCorrect following Item  Elevator lobby on 4th floorEmergency lighting must be on local lighting circuit or on dedicated circuit in an area with no less than 3 lighting circuits.
12/27/2023TransferCorrect following Item  ThroughoutAll luminaires require 2 seismic wires installed on opposite corners. Additionally, either all 4 tabs must hook over and under the top edge of the grid or have the other 2 corners screwed to the grid.