| Date | Status | Code | Description | Ref | Location | Comments |
| 12/27/2023 | Transfer | Correct following Item | | | 4th floor | No power at emergency lights at grid 4D and 5B. |
| 12/27/2023 | Transfer | Correct following Item | | | Elevator lobby on 4th floor | Emergency lighting must be on local lighting circuit or on dedicated circuit in an area with no less than 3 lighting circuits. |
| 12/27/2023 | Transfer | Correct following Item | | | Throughout | All luminaires require 2 seismic wires installed on opposite corners. Additionally, either all 4 tabs must hook over and under the top edge of the grid or have the other 2 corners screwed to the grid. |