Inspection #: 783233
Inspection Type: Other - Plubming
Inspector: K.Hanson
Result: Partial
Comment: Gas rough & test approved serving 1-boiler, 1-WH & 1-RTU, greentag issued. NOTE: RPBA (ASSE 1013) not required to serve boiler make-up water, Watts 9-D (ASSE 1012) sufficient & stated in plans. if RP is to be utilized, it shall be mounted no greater than 5' AFF as well as tested & tagged annually.