Inspection #: 782435
Inspection Type: Final Plumbing
Inspector: K.Hanson
Result: Partial
Comment: Partial Plumbing Final - Approved Correction regarding support/flexes addressed, Superior Plumbing scope of work complete. NOTE 1: Gas piping incomplete to RTUs, work to be performed by licensed plumbers. NOTE 2: Gas piping run in front of serviceable panels, 3' clearance required per NEC. May be an issue for Electrical inspector.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/14/2023CorrectedPlumbFinalCommentsSee Inspector CommentsRooftop & meter "Metraflexes"Remove angle from flexes to allow for movement. more substantial support may be required after meter flex is free to move.