Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 781947
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Corrections made. Electrical final approved except as noted. Submit AFC drawing to MOA plan review for change order. Include the required tested series combination labeling on plan in change order.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/19/2023CorrectedCorrect Below* Cash wrapUnder cash wrap secure and support mc and liquid tight. Connection of liquid tight to rigid pipe is detached not able to put eyes on it. Felt exposed conductors.
10/19/2023CorrectedCorrect Below* Roof top RTUProvide working clearance in front of RTU electrical components. Gas piping in area.
10/19/2023CorrectedCorrect Below* PanelsPost available fault current and date calculated
10/19/2023CorrectedCorrect Below* 4 gang switch boxBlank off switches that have no function.
10/19/2023CorrectedCorrect Below* Changing room areaChandelier remains to be installed
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter