Inspection #: 781460
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: see correction

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/16/2023TransferCorrect Below* Conduit supplying chiller.Conduit is within 110.26 working clearances of electrical compartment containing breakers, etc. Liquidtight Flexible Metal Conduit is required to be fastened within 12 inches of enclosures and at intervals not exceeding 4-1/2 ft.