| Date | Status | Code | Description | Ref | Location | Comments |
| 10/6/2023 | Corrected | Correct Below | * | | Through out | Several receptacles have an open ground on receptacle. If there is no grounding conductor at these locations all these receptacle shall be AFCI , GFCI protected. |
| 10/6/2023 | Corrected | Correct Below | * | | Laundry bathroom area | All receptacles in this area shall be GFCI protected and washer circuit the gfci function shall be an breaker and not receptacle. |
| 10/6/2023 | Corrected | Correct Below | * | | Exterior | Receptacle near front door shall be GFCI protected and have an extra duty rated in use cover. |
| 10/6/2023 | Corrected | Correct Below | * | | | Receptacles have an open ground and GFCI receptacle does not function. All receptacles in the kitchen shall be GFCI protected. If replaced will need to be tamper resistant and AFCI protected as well. |