Inspection #: 779686
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: electrical final approved conditionally until 11/3/23 pending completion of noted items

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/3/2023TransferCorrect Below*  Plans show floor box in dining area but work is incomplete. Complete floor box or provide field change order to remove from plans.
10/3/2023TransferCorrect Below*  Test button for em light incomplete.
10/3/2023TransferCorrect Below*  Verify/update panel schedules.
10/3/2023TransferCorrect Below*  Switch for new pump incomplete.
10/3/2023TransferCorrect Below*  Exit light at entrance incomplete.
10/3/2023TransferCorrect Below*  Pendant light incomplete.
10/3/2023TransferCorrect Below*  Seismic wires required at new track lights and pendant.
10/2/2023CorrectedCorrect Below*  GFCI protection required for 2 receptacles at west end of engine room in food service area.