Inspection #: 778484
Inspection Type: Final Fire Inspection
Inspector: B.Meinhardt
Result: CondAppr
Comment: Requested by: Ryan montgomery 9072329470

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
11/3/2023 Fire 2CCO approvalFire Final approved for CCO CCO approved till November 22, 2023 for installation of furniture and fixtures.
11/3/2023 Fire 15Correction(s) #2Please correct the following: Relocate 2 sprinkler heads that are less than 12 inches from the new track lighting.
11/3/2023 Fire 13Correction(s) #1Please correct the following: Replace all fire sprinkler concealer cover that have been painted black.