DateStatusCodeDescriptionRefLocationComments
10/19/2023TransferCorrect Below* Cash wrapUnder cash wrap secure and support mc and liquid tight. Connection of liquid tight to rigid pipe is detached not able to put eyes on it. Felt exposed conductors.
10/19/2023TransferCorrect Below* Roof top RTUProvide working clearance in front of RTU electrical components. Gas piping in area.
10/19/2023TransferCorrect Below* PanelsPost available fault current and date calculated
10/19/2023TransferCorrect Below* 4 gang switch boxBlank off switches that have no function.
10/19/2023TransferCorrect Below* Changing room areaChandelier remains to be installed