Inspection #: 776909
Inspection Type: Refrigeration Rough
Inspector: E.Huckaba
Result: Partial
Comment: AC line set and condensate rough in, test and inspection- APPROVED PER PLANS. NOTES: 5/8" LINE SET AND 1-1/8" CONDENSATE LINE FROM GROUND FLOOR AHU-1 TO THE ROOF TO AC-101 AND LINE SET FOR CRAC 302B- OK TO INSULATE AND COVER.