Inspection #: 774937
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: Inspection to observe operation of (1) of (2) shunt trip disconnects required / agreed to as a condition for having (2) utility services on (1) multi-tenant building. Remote shunt trip for Little Caesar's function confirmed. Location on building exterior is approved based on south end utility service moving to building exterior as originally intended. New corrections specific to the Little Caesar's service shunt trip. Other corrections from inspection #734215 dated 9/30/2022 remain to be resolved.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/6/2023TransferCorrect Below* NEW CORRECTION ITEM 9/6/2023. Safety switch style shunt trip at building south end to disconnect Little Caesar's.1. The "off" position is required to disconnect the power. See CEA ESR page 28, Section 306.7 and Policy E04. 2. Shunt trip does not have signage as per Policy E04.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Existing south end service requires new, main service disconnect / OCPD. New service OCPD to be shunt-trip type breaker with shunt trip actuator to be installed by Little Caesar's service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022CorrectedCorrect Below* Special permission item for (2) services on (1) building.Little Caesar's service OCPD required to be replaced with shunt-trip type breaker and shunt trip actuator installed by south end service. NOTE: TIMELINE FOR COMPLETION REQUIRED BY 10/25/2022.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.Mall wiring is currently disconnected in Little Caesar"s soffit. Reconnect those soffit lights to Little Caesar"s and reconnect Silk restaurant soffit lights to Mall house panel. NOTE: COMPLETE BY 10/25/2022 AND REQUEST REINSPECTION.
9/26/2022TransferCorrect Below* Special permission item for (2) services on (1) building.NEC 230.2(E) requires placarding with all specifics detailed in that section. NOTE: THERE IS TEMPORARY PLACCARDING THAT DOES NOT MEET THE SPECIFICS OF 230.2(E). CORRECT THIS BY 10/25/2022 AND REQUEST REINSPECTION.