Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 774827
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See Corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/28/2023CorrectedCorrect Below* Suite 3, 4 Proper labeling for Panel B Short Circuit Current Rating. 2020 NEC 408.6
8/28/2023CorrectedCorrect Below* Suite 3, 4Support MC and cable off of T-Bar ceiling.
8/28/2023CorrectedCorrect Below* Suite 4Breaker Blanks needed for panel B
8/28/2023CorrectedCorrect Below* Suite 5 electrical roomKo seal needed for 18" X 18" J-Box
8/28/2023CorrectedCorrect Below* Suite 5Emergency lighting not functioning.
8/28/2023TransferCorrect Below* Suite 5 Water Heater disconnect and connection to water heater remains to be installed. OCP for water heater appears to be oversized.
8/28/2023TransferCorrect Below* Suite 5 bathroom shower light remains to be installed. Light needs to support to structure. Flat metal plates that can be screwed to the grid are designed for this install.
8/28/2023TransferCorrect Below* Suite 5Prints show an egress light outside of front door remains to be installed. Exit sign is shown to have dual lights for egress lighting on the print.
8/28/2023TransferCorrect Below* Suite 5Prints show switch and light to be installed in electrical room. Light installed in electrical room shall not have ceiling tile support fixture. Light needs to support to structure. Flat metal plates that can be screwed to the grid are designed for this install.