Inspection #: 772563
Inspection Type: Final Plumbing
Inspector: K.Hanson
Result: Correction
Comment: Partial Plumbing Final - Approved See corrections & note. NOTE: Final gas connection to RTUs (3) incomplete.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/14/2023CorrectedPlumbFinalCommentsSee Inspector CommentsGas meterAs per 2018 IFGC 301.12 & 407.2 flex required to serve piping due to seismic forces & undue stress/strain on piping from uneven settling of meter/building.
8/14/2023TransferPlumbFinalCommentsSee Inspector CommentsRooftop & meter "Metraflexes"Remove angle from flexes to allow for movement. more substantial support may be required after meter flex is free to move.
8/14/2023CorrectedPlumbFinalCommentsSee Inspector CommentsRooftop gas regulatorsAs per local amendment to the 2018 IFGC 410.6, gas regulators shall be 2' above roof unless otherwise specified by manufacturer.
8/14/2023CorrectedPlumbFinalCommentsSee Inspector CommentsRooftop gas pipingAs per 2018 IFGC 410.2, all related unions, test tees & isolation valves shall be installed.