Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 772125
Inspection Type: Wall Rough Electrical
Inspector: M.Green
Result: Partial
Comment: Inspected various guest rooms on floors 2 and 3 and some bathrooms attached to the guest rooms. Electrical rough in guest rooms consists of extension from concealed wiring to surface wiring of receptacles at TV and at bed headboard. Surface work is to be concealed by removable head boards and cork boards. Electrical rough approved as follows: *Rooms 204, 219, 227 - surface rough as above. *Rooms 226, 228, 229 - surface rough as above and bathroom walls and ceilings. *Rooms 331, 332, 333, 334 - surface rough as above and bathroom walls and ceilings. IMPORTANT NOTE: ATLAS ELECTRIC IS SHOWN AS THE PERMITTEE. IF TUCK ELECTRIC IS A NEW PERMITTEE, CORRECT THE INFO ON THE PERMIT.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/5/2023TransferCorrect rough-in item below*  Corridors where ceiling grid has been removed must have electrical work corrected to meet current NEC requirements.
3/20/2023TransferCorrect rough-in item below*  Verify fire separation method for junction boxes between rooms
3/20/2023TransferCorrect rough-in item below* PTAC unitsWhite wire not permitted to be rephrased as green. Disconnect from grounds and safe off.
3/20/2023TransferCorrect rough-in item below* bathroomsBathroom backlit mirror whips incomplete.