Inspection #: 770492
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: Alan is offsite. Call Prior. We have two permits we would like to schedule to complete at the same time. E23-1704 + E23-1703 907-519-3569 Requested by: Nicholas Therrien 9073134600 nt@polarelectric.co

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
9/26/2023TransferCorrect Below*  Listing label for elevator controller indicates 3ph 480V 40hp motor. Disconnect only rated for 30hp at 3ph 480V.