| Date | Status | Code | Description | Ref | Location | Comments |
| 7/12/2023 | | Correct Below | * | | Bond metal enclosure lid. Conductive parts likely to be energized. See 250.4 | |
| 7/12/2023 | | Correct Below | * | | Service and lift station not yet energized or functioning. | |
| 7/12/2023 | | Correct Below | * | | Breaker lock required for heat trace. See 427.55 and 110.25. | |
| 7/12/2023 | | Correct Below | * | | Bond raceways with equipment grounding conductor. This correction remains from previous. | |
| 7/12/2023 | | Correct Below | * | | Ground rods required (2), unless meeting exception. See 250.53 A2 or exception. | |