Inspection #: 765654
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: Please call Eric prior to arrival 907 351 3464 Requested by: Jim mcallen 9072401130 mcallenelectric@hotmail.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/28/2023TransferCorrect Below* Suite 3, 4 Proper labeling for Panel B Short Circuit Current Rating. 2020 NEC 408.6
8/28/2023TransferCorrect Below* Suite 3, 4Support MC and cable off of T-Bar ceiling.
8/28/2023TransferCorrect Below* Suite 4Breaker Blanks needed for panel B
8/28/2023TransferCorrect Below* Suite 5 electrical roomKo seal needed for 18" X 18" J-Box
8/28/2023TransferCorrect Below* Suite 5Emergency lighting not functioning.
8/28/2023TransferCorrect Below* Suite 5 Water Heater disconnect and connection to water heater remains to be installed.
8/28/2023TransferCorrect Below* Suite 5 bathroom shower light remains to be installed.
8/28/2023TransferCorrect Below* Suite 5Prints show an egress light outside of front door remains to be installed.
8/28/2023TransferCorrect Below* Suite 5Prints show switch and light to be installed in electrical room.