Date | Status | Code | Description | Ref | Location | Comments |
8/28/2023 | Transfer | Correct Below | * | | Suite 3, 4 | Proper labeling for Panel B Short Circuit Current Rating. 2020 NEC 408.6 |
8/28/2023 | Transfer | Correct Below | * | | Suite 3, 4 | Support MC and cable off of T-Bar ceiling. |
8/28/2023 | Transfer | Correct Below | * | | Suite 4 | Breaker Blanks needed for panel B |
8/28/2023 | Transfer | Correct Below | * | | Suite 5 electrical room | Ko seal needed for 18" X 18" J-Box |
8/28/2023 | Transfer | Correct Below | * | | Suite 5 | Emergency lighting not functioning. |
8/28/2023 | Transfer | Correct Below | * | | Suite 5 | Water Heater disconnect and connection to water heater remains to be installed. |
8/28/2023 | Transfer | Correct Below | * | | Suite 5 bathroom | shower light remains to be installed. |
8/28/2023 | Transfer | Correct Below | * | | Suite 5 | Prints show an egress light outside of front door remains to be installed. |
8/28/2023 | Transfer | Correct Below | * | | Suite 5 | Prints show switch and light to be installed in electrical room. |