Inspection #: 764734
Inspection Type: Service
Inspector: M.Green
Result: Correction
Comment: Pedestal style electrical service to supply remote branch circuit panel and lift station control panel temporarily approved until 8/15/2023 to correct items below. Tag #39589. Correct items below and request reinspection. Note: MOA Building Safety did not inspect any underground related to this project or any of the seals before pouring.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/29/2023TransferCorrect service item below* Remote branch circuit panel.Verify installation of ground rods.
6/29/2023TransferCorrect service item below* Conduits from hazardous location lift station.Verify proper bonding of all metal conduits to all enclosures for both intrinsically safe system and power wiring all the way back to the service per 504.60 and 501.30.
6/29/2023TransferCorrect service item below* Intrinsically safe system conduits.Verify labelling per 504.80.
6/29/2023TransferCorrect service item below* Remote lift station control panel.Verify separation of any intrinsically safe system conductors within the control panel from non-intrinsically safe conductors per 504.30(A)(2).
6/29/2023TransferCorrect service item below* Remote lift station control panel. Will need to verify proper pouring of sealing fittings.
6/29/2023TransferCorrect service item below* Remote branch circuit panel.Install panel schedule.
6/29/2023TransferCorrect service item below* Remote branch circuit panel.Requires breaker blank.
6/29/2023TransferCorrect service item below* ServiceRequires available fault current labelling with date calculated.