Inspection #: 764732
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Requested by: Amanda Piaskowski 907-388-8937 tstokes@ccielectricalservices.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
7/12/2023TransferCorrect Below* Bond metal enclosure lid. Conductive parts likely to be energized. See 250.4 
7/12/2023TransferCorrect Below* Service and lift station not yet energized or functioning.  
7/12/2023TransferCorrect Below* Breaker lock required for heat trace. See 427.55 and 110.25.  
7/12/2023TransferCorrect Below* Bond raceways with equipment grounding conductor. This correction remains from previous.  
7/12/2023TransferCorrect Below* Ground rods required (2), unless meeting exception. See 250.53 A2 or exception.  