Inspection #: 764267
Inspection Type: Fire Sprinkler Final
Inspector: B.Meinhardt
Result: Partial
Comment: Mike McDonnell 907-354-7273 Requested by: Michael Wilcheck 907-344-3473 mwilcheck@chinookfire.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/29/2024Transferfiresprinkl17Correction(s) #4<div>Correct the following item(s):</div><div><br></div> Update hydraulic calc plates to show actual pressures at the base of riser verse at the street connection.&nbsp;
3/29/2024Transferfiresprinkl16Correction(s) #3<div>Correct the following item(s):</div><div><br></div> Missing hanger at top of riser on dry sprinkler system
3/29/2024Transferfiresprinkl15Correction(s) #2<div>Correct the following item(s):</div><div><br></div> Paints sprinkler heads in southwest stairwell and 3rd floor bathrooms
3/29/2024Transferfiresprinkl12SignageProvide signage for FDC, bell and other fire service items. Install FDC signs
3/29/2024Transferfiresprinklr14Correction(s) #1<div>Correct the following item(s):</div><div><br></div> Provide all required signage on valve, drains, Maps showing low point drains, general information signs, etc per 2019 NFPA 13 requirements.&nbsp;
3/29/2024Transferfiresprinkl13CCO ApprovedCCO approved for fire sprinkler system Fire sprinkler system approved for CCO till June 1, 2024
3/29/2024Transferfiresprinkl3Install cert <p class="MsoNormal"><font face="Times New Roman">Provide Installation Certification and test report.</font></p> <div><br> </div>  Provide installer certifications