Inspection #: 762885
Inspection Type: Final Plumbing
Inspector: K.Hanson
Result: Correction
Comment: Partial Plumbing Final - Approved CCO given, expires 10-16-23. DO NOT USE BATHROOM/SHOWER prior to approved inspection. See corrections. NOTE: Incomplete items to include the install of 1 of 2 double comp sinks & WC inoperable.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
8/16/2023TransferPlumbFinal1WaterTempTub/Shower<em>Tub/shower water temperature is required to be between 110-120 degress fahreneit- UPC 418 and local amendment 419</em>ShowerTemp witnessed at 83.1f
8/16/2023TransferPlumbFinalCommentsSee Inspector Comments2-comp sinkLeak witnessed.