Inspection #: 761186
Inspection Type: Plumbing Rough
Inspector: Y.Dovba
Result: Correction
Comment: Dwv and water piping rough-in and tests Approved. 1-Restrooms, 1-shower and 1-break room sink. NOTE: Depending on the use of the facility ASSE 1070 temp valves maybe required on lav's at final

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
6/14/2023TransferPlumbRgh14CommentsSee Inspectors CommentsDomestic water piping.Per 2018 UPC section 609.10 hammer arresters are required to be installed. NOTE: Hammer arresters will be inspected at final.