Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 758881
Inspection Type: Ceiling Rough Electrical
Inspector: O.Burbridge
Result: Correction
Comment: See corrections for 3rd floor ceiling.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/9/2024TransferEC1Correct Below  Exit signs require seismic support wires.
2/9/2024TransferEC1Correct Below  Wiring must be at least 1 1/2" beneath lowest part of pan decking of roof.
2/9/2024TransferEC1Correct Below  Each luminaire must be securely fastened to grid with 2 screws in opposite corners or 4 clips that connect to grid.
2/9/2024TransferEC1Correct Below  Close all junction boxes in ceiling.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS