| Date | Status | Code | Description | Ref | Location | Comments |
| 4/18/2023 | | Correct Below | * | | Drivers supplying class 2 power to sign on southeast wall. | 680.24(A) requires that class 2 power supplies are listed for use with electric signs -OR- a component of a listed sign. Drivers are not listed (only UR marked). Verify that drivers are covered under the sign listing. |
| 4/18/2023 | | Correct Below | * | | Class 2 cables. | 600.33(A) requires listed cables of a type specified in Table 600.33(A)(1) or Table 600.33(A)(2). Verify listing and proper type. 600.33(B)(1) requires Class 2 cables installed exposed to be supported so that the cables are not damaged in normal building use. |
| 4/18/2023 | | Correct Below | * | | Class 2 sign wiring that penetrates exterior stair wall to supply LED sign letters. | Also a violation of IBC 1023.5. |
| 4/18/2023 | | Correct Below | * | | EMT installed to serve original driver panel location in stairway. | EMT penetrates interior exit stairway enclosure. IBC 1023.5 prohibits installation of any wiring method in stairway that does not serve essential stairway equipment. |
| 4/18/2023 | | Correct Below | * | | Class 2 wiring for southeast facing sign. | Wiring penetrates 8th floor interior exit stairway enclosure. IBC 1023.5 prohibits installation of any wiring not serving equipment essential for the stairway. |