Inspection #: 755975
Inspection Type: Final Electrical
Inspector:
Result:
Comment:

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2023 Correct Below* Drivers supplying class 2 power to sign on southeast wall.680.24(A) requires that class 2 power supplies are listed for use with electric signs -OR- a component of a listed sign. Drivers are not listed (only UR marked). Verify that drivers are covered under the sign listing.
4/18/2023 Correct Below* Class 2 cables.600.33(A) requires listed cables of a type specified in Table 600.33(A)(1) or Table 600.33(A)(2). Verify listing and proper type. 600.33(B)(1) requires Class 2 cables installed exposed to be supported so that the cables are not damaged in normal building use.
4/18/2023 Correct Below* Class 2 sign wiring that penetrates exterior stair wall to supply LED sign letters.Also a violation of IBC 1023.5.
4/18/2023 Correct Below* EMT installed to serve original driver panel location in stairway.EMT penetrates interior exit stairway enclosure. IBC 1023.5 prohibits installation of any wiring method in stairway that does not serve essential stairway equipment.
4/18/2023 Correct Below* Class 2 wiring for southeast facing sign.Wiring penetrates 8th floor interior exit stairway enclosure. IBC 1023.5 prohibits installation of any wiring not serving equipment essential for the stairway.