Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 754807
Inspection Type: Wall Rough Electrical
Inspector: O.Burbridge
Result: Partial
Comment: electrical rough in for rooms 220-227, 326-330 approved

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/5/2023TransferCorrect rough-in item below*  Corridors where ceiling grid has been removed must have electrical work corrected to meet current NEC requirements.
3/20/2023TransferCorrect rough-in item below*  Verify fire separation method for junction boxes between rooms
3/20/2023TransferCorrect rough-in item below* PTAC unitsWhite wire not permitted to be rephrased as green. Disconnect from grounds and safe off.
3/20/2023TransferCorrect rough-in item below* bathroomsBathroom backlit mirror whips incomplete.
ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS