Inspection #: 754427
Inspection Type: Final Electrical
Inspector: M.Green
Result: Correction
Comment: C-permit scope of work is (4) new illuminated signs. Samson Electric's scope of work is to provide a 20A, 120V circuit for an 8th floor, southeast side, exterior LED sign. Sign drivers are in a cabinet above a T-bar grid ceiling in a storage room adjacent to an exit stair. Corrections are a mix of IBC and NEC Article 600 violations.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/18/2023TransferCorrect Below* Drivers supplying class 2 power to sign on southeast wall.680.24(A) requires that class 2 power supplies are listed for use with electric signs -OR- a component of a listed sign. Drivers are not listed (only UR marked). Verify that drivers are covered under the sign listing.
4/18/2023TransferCorrect Below* Class 2 cables.600.33(A) requires listed cables of a type specified in Table 600.33(A)(1) or Table 600.33(A)(2). Verify listing and proper type. 600.33(B)(1) requires Class 2 cables installed exposed to be supported so that the cables are not damaged in normal building use.
4/18/2023TransferCorrect Below* Class 2 sign wiring that penetrates exterior stair wall to supply LED sign letters.Also a violation of IBC 1023.5.
4/18/2023TransferCorrect Below* EMT installed to serve original driver panel location in stairway.EMT penetrates interior exit stairway enclosure. IBC 1023.5 prohibits installation of any wiring method in stairway that does not serve essential stairway equipment.
4/18/2023TransferCorrect Below* Class 2 wiring for southeast facing sign.Wiring penetrates 8th floor interior exit stairway enclosure. IBC 1023.5 prohibits installation of any wiring not serving equipment essential for the stairway.