Inspection Type: Wall Rough Electrical
Inspector: O.Burbridge
Result: Correction
Comment: rough in for rooms 101-117, 119 approved room 100, 118 incomplete

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/5/2023TransferCorrect rough-in item below*  Corridors where ceiling grid has been removed must have electrical work corrected to meet current NEC requirements.
3/20/2023TransferCorrect rough-in item below*  Verify fire separation method for junction boxes between rooms
3/20/2023TransferCorrect rough-in item below* PTAC unitsWhite wire not permitted to be rephrased as green. Disconnect from grounds and safe off.
3/20/2023TransferCorrect rough-in item below* bathroomsBathroom backlit mirror whips incomplete.