Inspection #: 751129
Inspection Type: Wall Rough Electrical
Inspector: O.Burbridge
Result: Correction
Comment: inspected rooms 100-120 (except 105, 108, 118), 200-203, 208, 300-306, 308, 310; rough in approved except for bathroom walls where additional whips+ to be added to feed backlit mirrors

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/20/2023TransferCorrect rough-in item below*  Verify fire separation method for junction boxes between rooms
3/20/2023TransferCorrect rough-in item below* PTAC unitsWhite wire not permitted to be rephrased as green. Disconnect from grounds and safe off.
3/20/2023TransferCorrect rough-in item below* bathroomsBathroom backlit mirror whips incomplete.
3/6/2023CorrectedCorrect rough-in item below* throughout unitsJunction box for PTAC units must remain accessible.
3/6/2023TransferCorrect rough-in item below* bathrooms in unitsConnections to backlit mirrors required to be done per NEC wiring method.
3/6/2023CorrectedCorrect rough-in item below* bathrooms in unitsSupport required for all electrical conduits.
3/6/2023CorrectedCorrect rough-in item below* throughoutAll metal boxes with new or reused wiring required to be bonded.
3/6/2023TransferCorrect rough-in item below* throughout unitsProvide verification of third party listing on all furniture with electrical parts.
3/6/2023TransferCorrect rough-in item below* throughout unitsAdditional receptacles required to meet requirements of 210.60.