Inspection #: 750053
Inspection Type: Final Structural
Inspector: J.Bergstrom
Result: Correction
Comment: Partial inspection on floors 2 - 9 and penthouse. Corrections listed below apply to all floors unless specific level noted.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:2nd floor Shaft RmGasket rated shaft wall door.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Level 2 Mech. Shaft. Repair damage and removed GWB at existing rated walls. Note** Temp guardrails in place until perm. guardrails installed.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Level 5 Electrical RmComplete fire stopping around rated hard lid and penetrations. And complete fire rated signage.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Electrical RoomComplete fire stopping around mech. shaft at head of wall.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Fire rated doors.Thresholds at rated doors shall not exceed 3/4 inch in height above finish floor.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Mech. Shaft in Electrical Rm.Complete metal angle around fire damper.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Electrical RoomComplete rated wall signage.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following: Complete floor signage in stairwell for each level.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following: Complete bathroom and stairwell signage.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following: Make adjustments to all required fire doors to close and latch.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Electrical RoomProvide engineers judgment and special inspection report for electrical equipment floor penetrations.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Janitors closetFire stop floor sink drains with approved UL listed assembly.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following: Install Permanent address #'s.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following: Complete installation of exterior glazing.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:BathroomsComplete install of trash receptacles and mirrors.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:Electrical RoomFire stop open floor pipes that communicate with floors above and below.
3/1/2023TransferFNLSGFinal Structural OtherPlease correct the following:PenthouseFire stop missed penetrations and metal angle around fire dampers.