| Date | Status | Code | Description | Ref | Location | Comments |
| 2/17/2023 | Transfer | Correct Below | * | | | Generator and chillers on rooftop require disconnects to be no higher than 6'7" above work surface to centerline of handle in highest position. (404.8A) |
| 2/15/2023 | Transfer | Correct Below | * | | | basement connections for rooftop lighting incomplete |
| 2/15/2023 | Transfer | Correct Below | * | | | basement sump pump incomplete |
| 2/15/2023 | Transfer | Correct Below | * | | | breaker lock required for heat trace in south stairwell |