Inspection #: 749499
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: some corrections made- remaining items are exterior and corrections noted below

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
2/17/2023TransferCorrect Below*  Generator and chillers on rooftop require disconnects to be no higher than 6'7" above work surface to centerline of handle in highest position. (404.8A)
2/15/2023TransferCorrect Below*  basement connections for rooftop lighting incomplete
2/15/2023TransferCorrect Below*  basement sump pump incomplete
2/15/2023TransferCorrect Below*  breaker lock required for heat trace in south stairwell