| Date | Status | Code | Description | Ref | Location | Comments |
| 4/28/2023 | | Firealarm22 | Fire alarm Notes 1 | Fire Alarm Notes: | | Floor plan received showing decibel levels in the facility in alarm, sound levels range from 81 dBA to 110 dBA are within allowable code minimum and maximum levels. Minimum level is 60 dBA per 2018 IFC amendment AMC 23.45.907.5.2.1.3. Maximum level is 110 dBA per 2018 IFC Section 907.5.2.1.2 |
| 4/28/2023 | | firealarm12 | Fire Alarm approved CO | Fire Alarm approved CO | | Fire Alarm approved for CO. Inspection on 4/27/2023 at 7 PM with John Ryan with Northern Support Services. |