| Date | Status | Code | Description | Ref | Location | Comments |
| 2/15/2023 | Transfer | Correct Below | * | | | basement connections for rooftop lighting incomplete |
| 2/15/2023 | Transfer | Correct Below | * | | | basement sump pump incomplete |
| 2/15/2023 | Transfer | Correct Below | * | | | breaker lock required for heat trace in south stairwell |
| 2/2/2023 | Transfer | Correct Below | * | | | label service with available fault current and date calculated |
| 2/2/2023 | Transfer | Correct Below | * | | | shunt trip switch for generator requires labels |
| 2/2/2023 | Transfer | Correct Below | * | | | bathroom on mezzanine incomplete |
| 2/2/2023 | Transfer | Correct Below | * | | | Conduits on rooftop must be GRC or IMC per local amendment 300.4I. |
| 2/2/2023 | Transfer | Correct Below | * | | | Generator and chillers on rooftop require disconnects to be no higher than 6'7" above work surface to centerline of handle in highest position. (404.8A) |