Inspection #: 748095
Inspection Type: Plumbing Rough
Inspector: K.Hanson
Result: Partial
Comment: Partial Plumbing Rough - Approved To include the replacement of 1-shower valve cartridge & minimal extension of water & DWV piping related to 1-lav & 1-WC serving units 100 & 101, OK to cover. NOTE: Future requirements will entail test & inspection of all new plumbing related work prior to covering, address dissimilar metal separation issues (metal stud in contact w/ copper piping & fittings), shower drain piping shall be 2" where accessible for upsizing, nail plates required where piping is within 1" of stud face, proper support of piping & shower valves required, applied showerpan liners shall be tested (fill liner/shower compartment completely to rough threshold) & inspected prior to covering. All plumbing shall be installed per 2018 UPC. More requirements may arise as project moves forward.