Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 748094
Inspection Type: Final Plumbing
Inspector: Y.Dovba
Result: Correction
Comment: Partial plumbing final Approved. 2nd floor rooms only: #200, 201, 210. NOTES: rooms requiring temperature adjustment: #202 shower temp is 100 degrees. #203 shower temp is 87 degrees. #204 shower temp is 70 degrees. #205 bathtub temp is 87 degrees. #206 temp is 90 degrees. #207 not trimmed out. #208 shower temp is 109 degrees. #212 temp is 109. #214 temp is 106 degrees. #216 temp is 97 degrees. #218 shower valve not trimmed out at this time. 3rd floor rooms. #300, 301, 302, 303, 304, 305, 306, 308. 310 and 312. these room toilets don't flush, shower valves not trimmed out, none of the plumbing fixtures are caulked. Please go through each of these rooms and adjust the water temperature to a minimum of 110 degree and a maximum of 120 degrees, be sure all toilets flush.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/16/2024CorrectedPlumbFinalCommentsSee Inspector Comments2nd and 3rd floor rooms.Restrooms requiring water temperature adjustment. Please see plumbing notes.