| Date | Status | Code | Description | Ref | Location | Comments |
| 1/24/2023 | Transfer | Correct Below | * | | | all disconnects mounted to bus work must have disconnecting means that meet NEC 404.8(A) exception 1 |
| 1/23/2023 | Corrected | Correct Below | * | | floor 9 | no power at receptacle in com room |
| 1/23/2023 | Corrected | Correct Below | * | | floor 8 | ko seal required at disconnect feeding panel- also label panel with source |
| 1/23/2023 | Corrected | Correct Below | * | | floors 8 and 9 | no power at exit signs |
| 1/23/2023 | Corrected | Correct Below | * | | floors 7, 8, 9 | gfci protection required within 6' of mop sink in janitor closets |
| 1/20/2023 | Transfer | Correct Below | * | | south stair well/exit enclosure. | Throughout-Wiring not associated with exit enclosure that was partially demoed remains. If not part of the required equipment for the exit enclosure, wiring is required to be removed. Does not appear to be required wiring for the stairwell exit enclosure. Additionally, if allowed to remain as part of the required equipment for the stairwell/exit enclosure, MC cable hanging, boxes hanging, some raceways require additional support, open boxes/receptacles without covers, etc. |
| 1/20/2023 | Transfer | Correct Below | * | | North and south stairwells. | Cabinet unit heaters required to be connected to 15 amp max OCP. |