Inspection #: 747105
Inspection Type: Final Electrical
Inspector: O.Burbridge
Result: Correction
Comment: progress final approved for floors 4,5,6,7,8,9 except for noted corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
1/24/2023TransferCorrect Below*  all disconnects mounted to bus work must have disconnecting means that meet NEC 404.8(A) exception 1
1/23/2023CorrectedCorrect Below* floor 9no power at receptacle in com room
1/23/2023CorrectedCorrect Below* floor 8ko seal required at disconnect feeding panel- also label panel with source
1/23/2023CorrectedCorrect Below* floors 8 and 9no power at exit signs
1/23/2023CorrectedCorrect Below* floors 7, 8, 9gfci protection required within 6' of mop sink in janitor closets
1/20/2023TransferCorrect Below* south stair well/exit enclosure. Throughout-Wiring not associated with exit enclosure that was partially demoed remains. If not part of the required equipment for the exit enclosure, wiring is required to be removed. Does not appear to be required wiring for the stairwell exit enclosure. Additionally, if allowed to remain as part of the required equipment for the stairwell/exit enclosure, MC cable hanging, boxes hanging, some raceways require additional support, open boxes/receptacles without covers, etc.
1/20/2023TransferCorrect Below* North and south stairwells. Cabinet unit heaters required to be connected to 15 amp max OCP.