Click Here To View Another Inspection Inspection #: 745986 Inspection Type: Electrical Rough Inspector: N.Holland Result: Correction Comment: Work completed and approved in rooms 116, 126. See Corrections for Chiller ACC-2. Inspection Corrections DateStatusCodeDescriptionRefLocationComments 9/8/2023Transfer01See inspection comments Chiller ACC-22" LB's are undersized for 3- 3/0 conductors.