Inspection Type: Final Fire Inspection
Inspector: D.Meneses
Result: Correction
Comment: Please give me a call 10 mins prior Requested by: Tim Leedy 907-632-0683 TimL@criteriongeneral.com

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
4/28/2023 Fire 13Correction(s) #1Please correct the following: Fire sprinkler coverage is over spaced in the following areas:&nbsp;&nbsp;<div>Hall by Coffee room (132).&nbsp; &nbsp;</div><div>Hall (106) by reception desk leading to main lobby.&nbsp;&nbsp;</div><div>Main lobby (100) by glass wall separating conference 101 and lobby 100.&nbsp;&nbsp;</div><div><br></div><div>Entire remodel space need to be evaluated by a fire sprinkler company for code compliant coverage and provide installer certification.&nbsp;</div>
4/27/2023TransferFire 15Correction(s) #2Please correct the following: 1) need to have Fire extinguishers replaced or recertified with correct tag.&nbsp;&nbsp;