Click Here To View Another Inspection Inspection #: 744353 Inspection Type: Final Plumbing Inspector: E.Wood Result: Partial Comment: Low and medium pressure gas piping, and tests to 2 gas fireplaces, Approved. NOTES: #1. Ducting is already wrapped in insulation, this needs to be removed for inspection. #2. The exterior gas flex on the roof needs to have a full six inches of deflection. #3 Be sure the test 'T' is 6 pipe diameters down stream of the regulator. #4. Please replace the copper Unistrut clamp with a galvanized one. #5. The flue, the clearances, as well at the above mentioned notes will be looked at, on the next inspection. Inspection Corrections DateStatusCodeDescriptionRefLocationComments