| Date | Status | Code | Description | Ref | Location | Comments |
| 7/28/2023 | Transfer | Fire 19 | Correction(s) #6 | Please correct the following: | | Corrections 1 through 5 are moved over from permit C19-2451 and shall be completed before CCO of C22-2035. |
| 7/28/2023 | Transfer | Fire 18 | Correction(s) #5 | Please correct the following: | | Fire monitoring need to be operational. |
| 7/28/2023 | Transfer | Fire 17 | Correction(s) #4 | Please correct the following: | | Fire alarm changes in relation to addition of battery cabinets need to be completed in relation to change order X23-1440 |
| 7/28/2023 | Transfer | Fire 16 | Correction(s) #3 | Please correct the following: | | Need to verify that building keys are installed in knox box and any access control cards for fire department access. |
| 7/28/2023 | Transfer | Fire 13 | Correction(s) #1 | Please correct the following: | | Emergency Stairway call boxes are not operational and must be completed and in compliance with 2012 IBC 403.5.3.1. It has not been identified where the constantly attended station will be located and dial out to 3rd party monitoring. Note: communication between the stairwell and fire command center is working. Outside monitoring and security desk shall to be setup and operation before fire final CCO. Adjust call sequencing to 5 rings before transfer. Post building address and instruction on call stair call boxes. Post instructions in fire command center. |
| 7/28/2023 | Transfer | Fire 15 | Correction(s) #2 | Please correct the following: | | Provide all items required to be in the fire command center per 2012 IBC 403.4.6 and 911.1.5 items 1-18. 13 (13.1 and 13.2 will have to be addressed at TI buildouts), 13.3 one set of building plans as spaced get TI's completed, 17 Elevator recall switch in accordance with ASME A17.1 for existing 2 elevator in main lobby, 18 Elevator emergency or standby power selector switch(es). |