Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To View Another Inspection


Inspection #: 737874
Inspection Type: Final Electrical
Inspector: N.Holland
Result: Correction
Comment: See corrections

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/20/2022TransferCorrect Below* Therapy roomReceptacles on north wall have no power.
10/20/2022TransferCorrect Below* CeilingJboxes need cover plates.
10/20/2022TransferCorrect Below* X-ray roomReceptacle next to 2 gang blank has no power.
10/12/2022TransferCorrect Below* Panel Update panel schedule, make up is incomplete.
10/12/2022TransferCorrect Below* Throughout MC cable needs to be supported so it is not lying on suspended ceiling.
10/12/2022TransferCorrect Below* Patient care areasAll branch circuits serving these spaces shall be provided with an effective ground fault current path. 2017 NEC 517.13 A This includes circuits that go to light switches as well as receptacles.