Inspection #: 737860
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Electrical final ok for extension of conditional approval until 1/13/23.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2022TransferCorrect Below* Lounge equipmentRequired to be installed for inspection. Equipment ID's 9-16. Update: toaster and drink case incomplete.
10/14/2022TransferCorrect Below* Ice maker at kitchen and lounge. Max 15 amp ocp for lounge icemaker at lounge. Install instructions do not appear to specifically allow for cord connection. Instructions recommend to not connect to GFCI protected circuit. Hard wire connection with approved disconnect per 422.31 as required.
9/7/2022TransferCorrect Below* ATO / BCOOffice furniture not installed at this time.