Inspection #: 737125
Inspection Type: Final Electrical
Inspector: E.Widman
Result: Partial
Comment: Corrections made for Prep Kitchen ND206C Ice Bin, Dishwasher, Oven. , and type M2 “cloud light”, and Tools Maintenance ND103 mixed class1&2 wiring. Electrical final for Business Center ND206A, Lounge ND206, Kitchen ND206C, Theater ND264, Tools Maintenance ND103 areas conditionally approved for use until 11/15/22.

Inspection Corrections
DateStatusCodeDescriptionRefLocationComments
10/14/2022CorrectedCorrect Below* Tools and maintenanceHeaters incomplete. Thermostat low voltage wiring not separate from power wiring. Maintain separation from power wiring to use class 2 wiring method, or class 2 system must be installed in a chapter 3 method approved for the location.
10/14/2022TransferCorrect Below* Lounge equipmentRequired to be installed for inspection. Equipment ID's 9-16. Update: toaster and drink case incomplete.
10/14/2022CorrectedCorrect Below* "Cloud lights"See 411.6 (C). Required to be installed minimum of 7' above finished floor unless specifically listed for lower installation.
10/14/2022TransferCorrect Below* Ice maker at kitchen and lounge. Max 15 amp ocp for lounge icemaker at lounge. Install instructions do not appear to specifically allow for cord connection. Instructions recommend to not connect to GFCI protected circuit. Hard wire connection with approved disconnect per 422.31 as required.
10/14/2022CorrectedCorrect Below* Kitchen equipment-dish washer, oven/steamer.Do not appear to have third party listing and ratings labeled on equipment.
9/7/2022TransferCorrect Below* ATO / BCOOffice furniture not installed at this time.