| Date | Status | Code | Description | Ref | Location | Comments |
| 10/14/2022 | Corrected | Correct Below | * | | New AHU | 15 amp max overcurrent protection required for lighting circuit per manufacturer label. Provide plans for inspection, not provided for this inspection. Unable to verify install matches plans. Verify correct circuits are used for equipment and lighting. If alternates are used, provide field change order. Lighting circuit for AHU added to existing circuit 27. |